大功率UPS電源安裝設備場地與環境要求

admin 2019-04-29

   1、設備就位場地應為水平硬質地面。如果是防靜電活動地板,則需考慮地板的承受能力,應根據設備重量來設計與制造鋼質托架。就位場地應能得到所有必要的服務,尤其是光、電荷良好的通風。


   多數大、中型UPS標準機型的電纜為下進下出型。UPS機柜的通風進氣口位于機柜的正面或側面,出氣口在機柜的上部。為此,在安裝UPS蓄電池時,要求用戶事先準備好電纜敷設地溝,其深度為40cm左右。當用戶采用橋架電纜敷設方法時,應選用電纜為上進上出型的UPS機型。

   

    2、就為場地應沒有灰塵,尤其不應有導電性質的塵埃,否則可能會導致設備內部電路短路而影響UPSCGB蓄電池的可靠運行。同時,場地也不應具有或靠近熱源,以確保設備所規定的環境。

   

    3、為了便于操作、設備維修和設備散熱,應至少使設備機柜四周留有50~100cm的空間,上部留有100cm的空間。設計機房冷卻通風系統時,要來考慮UPS電源產生的熱量。

   

    4、UPS電源的工作環境溫度要求在0~35℃,最佳溫度為25℃左右。最佳濕度為30%~70%。